Column_1,Column_2
APPLICABLE CODES:,"GENERAL:
• BUILDING/DWELLING CODE IBC 2015 & AHJ AMENDMENTS
EXISTING:
ENERGY CONSERVATION:
• INTERNATIONAL ENERGY CONSERVATION CODE 2015 & AHJ AMENDMENTS
PLUMBING:
MECHANICAL:
• MECHANICAL CODE IMC 2015 & AHJ AMENDMENTS
ELECTRICAL:
• ELECTRICAL CODE NEC 2017 & AHJ AMENDMENTS
FIRE:
• FIRE/LIFE SAFETY CODE 2009 NFPA-1 & AHJ AMENDMENTS
ACCESSIBILITY:
• ANSI STANDARD A117.1-2009- FOR ACCESSIBILITY
FUEL:
• INTERNATIONAL FUEL GAS CODE 2015 & AHJ AMENDMENTS"
CHAPTER 3 USE AND OCCUPANCY CLASSIFICATION:,310.4 RESIDENTIAL GROUP R-2
"SECTION 420 GROUPS I-1, R-1, R-2, R-3 AND R-4","SECTION 420 GROUPS R-2
• FIRE PARTITIONS IN ACCORDANCE WITH SECTION 708
• HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH SECTION 711."
CHAPTER 5 CLASSIFICATION OF WORK:,NEW
504.3 HEIGHT IN FEET,"R-2 TYPE VB (SPRINKLERED):
• ACTUAL: 35FT
• ALLOWED: 60FT
"
504.4 NUMBER OF STORIES,"R-2 TYPE VB (SPRINKLERED):
• ACTUAL: 3
• ALLOWED: 4
"
"506.2 ALLOWABLE AREA DETERMINATION
&
506.3 FRONTAGE INCREASE:"," • TABULAR PER FLOOR AREA LIMIT PER CHAPTER 5 = 7000 SQ.FT.
• ALLOW HEIGHT = 60 FT; ALLOW STORIES = 3
• NFPA 13 SPRINKLERS
• COMPUTE AREA INCREASE DUE TO FRONTAGE: FRONTAGE COEFFICIENT, IF 0.589
• PERIMETER, P 354 FT
• 'FRONTAGE' PERIMETER, F 306 FT
• WEIGHTED AVERAGE DISTANCE FROM 'F' = 228.75 FT
• COMPUTE ALLOWABLE PER STORY AREA, AA = AT +(NS X IF) = 25120.94 SQ.FT.
• MAXIMUM ALLOWABLE AREA = AA X 3 = 75362.83 SQ.FT.
• MAXIMUM NUMBER OF STORIES FOR GROUP R WITH NFPA 13R SPRINKLERS, PER SEC. 903.3.1.2.THIS CRITERIA IS MET, SO STORY LIMIT = 3
• THE REVISED ALLOWABLE HEIGHT IS 60 FT.
ACTUAL
• (ALL FLOORS): 16,826SF
• FLOORS: 3"
508.3 NONSEPARATED OCCUPANCIES:,N/A
508.4 SEPARATED OCCUPANCIES,N/A
"TABLE 601
FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS (HOURS)","FOR TYPE VB
STRUCTURAL FRAME: 0 HR
BEARING WALLS- EXTERIOR: 0 HR
BEARING WALLS-INTERIOR: 0 HR
NON-BEARING WALLS-EXTERIOR (SEE TABLE 602)
NON-BEARING WALLS-INTERIOR: 0 HR
FLOOR CONSTRUCTION: 0 HR
ROOF CONSTRUCTION: 0 HR
"
"TABLE 602
FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE SEPARATION DISTANCE","TYPE-VB
FIRE SEPARATION DISTANCE
• X < 5C = 1 HR
• 5 ≤ X ≤ 10 = 1 HR
• 10 ≤ X ≤ 30 = 0 HR
• X ≥ 30 = 0 HR"
708.3 FIRE-RESISTANCE RATING,"CORRIDORS: 1/2HR RATED
DWELLING UNIT AND SLEEPING UNIT SEPARATIONS: 1/2HR RATED"
711.2.4.3 DWELLING UNITS AND SLEEPING UNITS,BETWEEN DWELLING UNITS: 1/2HR RATED
803.11 INTERIOR FINISH REQUIREMENTS BASED ON GROUP,"FOR SPRINKLERED R-2:
INTERIOR EXIT STAIRWAYS AND RAMPS AND EXIT PASSAGEWAYS: CLASS C
CORRIDORS AND ENCLOSURE FOR EXIT ACCESS STAIRWAYS AND RAMPS: CLASS C
ROOMS AND ENCLOSED: CLASS C"
SPRINKLERS (SECTION 903 AUTOMATIC SPRINKLER SYSTEMS):,NFPA13 SPRINKLER THROUGHOUT PROJECT (R-2)
SECTION 1020 CORRIDORS,"CORRIDORS: 1/2HR RATED
SEE SECTION 1021 EGRESS BALCONIES FOR CORRIDOR RATING AT EXTERIOR WALL"
SECTION 1004 OCCUPANT LOAD,"TABLE 1004.1.2
MAXIMUM FLOOR AREA ALLOWANCES PER OCCUPANT
RESIDENTIAL: 200 GROSS"
1006.2.1 EGRESS BASED ON OCCUPANT LOAD AND COMMON PATH OF EGRESS TRAVEL DISTANCE:,"FOR R-2
MAXIMUM COMMON PATH WITH SPRINKLER SYSTEM: 125FT
MAXIMUM OCCUPANT LOAD OF SPACE WITH ONE EXIT: 49
"
SECTION 1017 EXIT ACCESS TRAVEL DISTANCE:,"FOR R-2: 250 (W/SPRINKLER)
"
1020.4 DEAD ENDS:,50FT (WITH NFPA13 SPRINKLERS)
SECTION 1021 EGRESS BALCONIES,"EXTERIOR EGRESS BALCONIES SHALL BE SEPARATED FROM THE INTERIOR OF THE BUILDING BY WALLS AND OPENING PROTECTIVES AS REQUIRED FOR CORRIDORS.
SECTION 1020 CORRIDORS 1020.1 CONSTRUCTION
CORRIDORS SHALL BE FIRE-RESISTANCE-RATED IN ACCORDANCE WITH TABLE 1020.1. THE CORRIDOR WALLS REQUIRED TO BE FIRE-RESISTANCE-RATED SHALL COMPLY WITH SECTION 708 FOR FIRE PARTITIONS.
EXCEPTIONS:
CORRIDORS ADJACENT TO THE EXTERIOR WALLS OF BUILDINGS SHALL BE PERMITTED TO HAVE UNPROTECTED OPENINGS ON UNRATED EXTERIOR WALLS WHERE UNRATED WALLS ARE PERMITTED BY TABLE 602 AND UNPROTECTED OPENINGS ARE PERMITTED BY TABLE 705.8."
2902.1 MINIMUM NUMBER OF FIXTURES,"CLASSIFICATION & OCCUPANCY:
---
R-2
• WATER CLOSETS: 1 PER DWELLING
• LAVATORIES: 1 PER DWELLING
• BATHTUBS/ SHOWERS: 1 PER DWELLING"
1 Column_1 Column_2
2 APPLICABLE CODES: GENERAL: • BUILDING/DWELLING CODE IBC 2015 & AHJ AMENDMENTS EXISTING: ENERGY CONSERVATION: • INTERNATIONAL ENERGY CONSERVATION CODE 2015 & AHJ AMENDMENTS PLUMBING: MECHANICAL: • MECHANICAL CODE IMC 2015 & AHJ AMENDMENTS ELECTRICAL: • ELECTRICAL CODE NEC 2017 & AHJ AMENDMENTS FIRE: • FIRE/LIFE SAFETY CODE 2009 NFPA-1 & AHJ AMENDMENTS ACCESSIBILITY: • ANSI STANDARD A117.1-2009- FOR ACCESSIBILITY FUEL: • INTERNATIONAL FUEL GAS CODE 2015 & AHJ AMENDMENTS
3 CHAPTER 3 USE AND OCCUPANCY CLASSIFICATION: 310.4 RESIDENTIAL GROUP R-2
4 SECTION 420 GROUPS I-1, R-1, R-2, R-3 AND R-4 SECTION 420 GROUPS R-2 • FIRE PARTITIONS IN ACCORDANCE WITH SECTION 708 • HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH SECTION 711.
5 CHAPTER 5 CLASSIFICATION OF WORK: NEW
6 504.3 HEIGHT IN FEET R-2 – TYPE VB (SPRINKLERED): • ACTUAL: 35FT • ALLOWED: 60FT
7 504.4 NUMBER OF STORIES R-2 – TYPE VB (SPRINKLERED): • ACTUAL: 3 • ALLOWED: 4
8 506.2 ALLOWABLE AREA DETERMINATION & 506.3 FRONTAGE INCREASE: • TABULAR PER FLOOR AREA LIMIT PER CHAPTER 5 = 7000 SQ.FT. • ALLOW HEIGHT = 60 FT; ALLOW STORIES = 3 • NFPA 13 SPRINKLERS • COMPUTE AREA INCREASE DUE TO FRONTAGE: FRONTAGE COEFFICIENT, IF 0.589 • PERIMETER, P 354 FT • 'FRONTAGE' PERIMETER, F 306 FT • WEIGHTED AVERAGE DISTANCE FROM 'F' = 228.75 FT • COMPUTE ALLOWABLE PER STORY AREA, AA = AT +(NS X IF) = 25120.94 SQ.FT. • MAXIMUM ALLOWABLE AREA = AA X 3 = 75362.83 SQ.FT. • MAXIMUM NUMBER OF STORIES FOR GROUP R WITH NFPA 13R SPRINKLERS, PER SEC. 903.3.1.2.THIS CRITERIA IS MET, SO STORY LIMIT = 3 • THE REVISED ALLOWABLE HEIGHT IS 60 FT. ACTUAL • (ALL FLOORS): 16,826SF • FLOORS: 3
9 508.3 NONSEPARATED OCCUPANCIES: N/A
10 508.4 SEPARATED OCCUPANCIES N/A
11 TABLE 601 FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS (HOURS) FOR TYPE VB STRUCTURAL FRAME: 0 HR BEARING WALLS- EXTERIOR: 0 HR BEARING WALLS-INTERIOR: 0 HR NON-BEARING WALLS-EXTERIOR – (SEE TABLE 602) NON-BEARING WALLS-INTERIOR: 0 HR FLOOR CONSTRUCTION: 0 HR ROOF CONSTRUCTION: 0 HR
12 TABLE 602 FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE SEPARATION DISTANCE TYPE-VB FIRE SEPARATION DISTANCE • X < 5C = 1 HR • 5 ≤ X ≤ 10 = 1 HR • 10 ≤ X ≤ 30 = 0 HR • X ≥ 30 = 0 HR
13 708.3 FIRE-RESISTANCE RATING CORRIDORS: 1/2HR RATED DWELLING UNIT AND SLEEPING UNIT SEPARATIONS: 1/2HR RATED
14 711.2.4.3 DWELLING UNITS AND SLEEPING UNITS BETWEEN DWELLING UNITS: 1/2HR RATED
15 803.11 INTERIOR FINISH REQUIREMENTS BASED ON GROUP FOR SPRINKLERED R-2: INTERIOR EXIT STAIRWAYS AND RAMPS AND EXIT PASSAGEWAYS: CLASS C CORRIDORS AND ENCLOSURE FOR EXIT ACCESS STAIRWAYS AND RAMPS: CLASS C ROOMS AND ENCLOSED: CLASS C
16 SPRINKLERS (SECTION 903 AUTOMATIC SPRINKLER SYSTEMS): NFPA13 SPRINKLER THROUGHOUT PROJECT (R-2)
17 SECTION 1020 CORRIDORS CORRIDORS: 1/2HR RATED SEE SECTION 1021 EGRESS BALCONIES FOR CORRIDOR RATING AT EXTERIOR WALL
18 SECTION 1004 OCCUPANT LOAD TABLE 1004.1.2 MAXIMUM FLOOR AREA ALLOWANCES PER OCCUPANT RESIDENTIAL: 200 GROSS
19 1006.2.1 EGRESS BASED ON OCCUPANT LOAD AND COMMON PATH OF EGRESS TRAVEL DISTANCE: FOR R-2 MAXIMUM COMMON PATH WITH SPRINKLER SYSTEM: 125FT MAXIMUM OCCUPANT LOAD OF SPACE WITH ONE EXIT: 49
20 SECTION 1017 EXIT ACCESS TRAVEL DISTANCE: FOR R-2: 250 (W/SPRINKLER)
21 1020.4 DEAD ENDS: 50FT (WITH NFPA13 SPRINKLERS)
22 SECTION 1021 EGRESS BALCONIES EXTERIOR EGRESS BALCONIES SHALL BE SEPARATED FROM THE INTERIOR OF THE BUILDING BY WALLS AND OPENING PROTECTIVES AS REQUIRED FOR CORRIDORS. SECTION 1020 CORRIDORS 1020.1 CONSTRUCTION CORRIDORS SHALL BE FIRE-RESISTANCE-RATED IN ACCORDANCE WITH TABLE 1020.1. THE CORRIDOR WALLS REQUIRED TO BE FIRE-RESISTANCE-RATED SHALL COMPLY WITH SECTION 708 FOR FIRE PARTITIONS. EXCEPTIONS: CORRIDORS ADJACENT TO THE EXTERIOR WALLS OF BUILDINGS SHALL BE PERMITTED TO HAVE UNPROTECTED OPENINGS ON UNRATED EXTERIOR WALLS WHERE UNRATED WALLS ARE PERMITTED BY TABLE 602 AND UNPROTECTED OPENINGS ARE PERMITTED BY TABLE 705.8.
23 2902.1 MINIMUM NUMBER OF FIXTURES CLASSIFICATION & OCCUPANCY: --- R-2 • WATER CLOSETS: 1 PER DWELLING • LAVATORIES: 1 PER DWELLING • BATHTUBS/ SHOWERS: 1 PER DWELLING