2APPLICABLE CODES:GENERAL: • BUILDING/DWELLING CODE IBC 2015 & BRYAN,TX AMENDMENTS ENERGY CONSERVATION: • INTERNATIONAL ENERGY CONSERVATION CODE 2015 & BRYAN,TX AMENDMENTS PLUMBING: • PLUMBING CODE IMC 2015 & BRYAN,TX AMENDMENTS MECHANICAL: • MECHANICAL CODE IMC 2015 & BRYAN,TX AMENDMENTS ELECTRICAL: • ELECTRICAL CODE NEC 2020 & BRYAN,TX AMENDMENTS FIRE: • FIRE/LIFE SAFETY CODE 2009 NFPA-1 & BRYAN,TX AMENDMENTS ACCESSIBILITY: • ANSI STANDARD A117.1-2009- FOR ACCESSIBILITY • FAIR HOUSING ACT FUEL: • INTERNATIONAL FUEL GAS CODE 2015 & BRYAN,TX AMENDMENTSGENERAL: • BUILDING/DWELLING CODE IBC 2015 • (WI COMMERCIAL BUILDING CODE SPS 362) EXISTING: • INTERNATIONAL EXISTING BUILDING CODE 2015 • (WI COMMERCIAL BUILDING CODE SPS 366) ENERGY CONSERVATION: • INTERNATIONAL ENERGY CONSERVATION CODE 2015 • (WI COMMERCIAL BUILDING CODE V363) PLUMBING: • WI COMMERCIAL BUILDING CODE SPS 381-387 MECHANICAL: • MECHANICAL CODE IMC 2015 • (WI COMMERCIAL BUILDING CODE SPS 364) ELECTRICAL: • ELECTRICAL CODE NEC 2017 • (WI COMMERCIAL BUILDING CODE SPS 316 FIRE: • FIRE/LIFE SAFETY CODE 2009 NFPA-1 • (WI COMMERCIAL BUILDING CODE SPS 314 & 330) ACCESSIBILITY: • ANSI STANDARD A117.1-2009- FOR ACCESSIBILITY • (WI COMMERCIAL BUILDING CODE SPS 362) FUEL: • INTERNATIONAL FUEL GAS CODE 2015 • (WI COMMERCIAL BUILDING CODE CHAPTER 365)
3CHAPTER 3 USE AND OCCUPANCY CLASSIFICATION:310.4 RESIDENTIAL GROUP R-2https://up.codes/viewer/texas/ibc-2015/chapter/3/use-and-occupancy-classification#3https://up.codes/viewer/texas/ibc-2015/chapter/3/use-and-occupancy-classification#3
4SECTION 420 GROUPS I-1, R-1, R-2, R-3 AND R-4SECTION 420 GROUPS R-2 • FIRE PARTITIONS IN ACCORDANCE WITH SECTION 708 • HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH SECTION 711.https://up.codes/viewer/texas/ibc-2015/chapter/4/special-detailed-requirements-based-on-use-and-occupancy#420https://up.codes/viewer/texas/ibc-2015/chapter/4/special-detailed-requirements-based-on-use-and-occupancy#420
5CHAPTER 5 CLASSIFICATION OF WORK:NEWhttps://up.codes/viewer/texas/iebc-2015/chapter/5/classification-of-work#5https://up.codes/viewer/texas/iebc-2015/chapter/5/classification-of-work#5
6504.3 HEIGHT IN FEETR-2 TYPE VB (SPRINKLERED): • ACTUAL: 35FT • ALLOWED: 60FT https://up.codes/viewer/texas/ibc-2015/chapter/5/general-building-heights-and-areas#504.3https://up.codes/viewer/texas/ibc-2015/chapter/5/general-building-heights-and-areas#504.3
7504.4 NUMBER OF STORIESR-2 TYPE VB (SPRINKLERED): • ACTUAL: 3 • ALLOWED: 4 https://up.codes/viewer/texas/ibc-2015/chapter/5/general-building-heights-and-areas#504.4https://up.codes/viewer/texas/ibc-2015/chapter/5/general-building-heights-and-areas#504.4
8506.2 ALLOWABLE AREA DETERMINATION & 506.3 FRONTAGE INCREASE: • TABULAR PER FLOOR AREA LIMIT PER CHAPTER 5 = 7000 SQ.FT. • ALLOW HEIGHT = 60 FT; ALLOW STORIES = 3 • NFPA 13 SPRINKLERS • COMPUTE AREA INCREASE DUE TO FRONTAGE: FRONTAGE COEFFICIENT, IF 0.589 • PERIMETER, P 354 FT • 'FRONTAGE' PERIMETER, F 306 FT • WEIGHTED AVERAGE DISTANCE FROM 'F' = 228.75 FT • COMPUTE ALLOWABLE PER STORY AREA, AA = AT +(NS X IF) = 25120.94 SQ.FT. • MAXIMUM ALLOWABLE AREA = AA X 3 = 75362.83 SQ.FT. • MAXIMUM NUMBER OF STORIES FOR GROUP R WITH NFPA 13R SPRINKLERS, PER SEC. 903.3.1.2.THIS CRITERIA IS MET, SO STORY LIMIT = 3 • THE REVISED ALLOWABLE HEIGHT IS 60 FT. ACTUAL • (ALL FLOORS): 16,826SF • FLOORS: 3https://up.codes/viewer/texas/ibc-2015/chapter/5/general-building-heights-and-areas#506.2https://up.codes/viewer/texas/ibc-2015/chapter/5/general-building-heights-and-areas#506.2FACING NORTH: • 174FT (60FT TO R.O.W) FACING EAST: • 145 (60FT TO R.O.W) FACING SOUTH: • 73FT (6FT TO P.L.) • 33FT (117FT TO P.L) • 73FT (6FT TO P.L.) FACING WEST: • 145FT (13FT TO P.L.) FOR R-2 • ALLOWABLE AREA PER FLOOR: 23,082SF (W/ FRONTAGE INCREASE) • ACTUAL • 1ST FLOOR:20,889SF • 2ND FLOOR:22,879SF • 3RD FLOOR: 22,957SF • TOTAL ALLOWABLE AREA:69,246SF • ACTUAL: 66,725SF FOR S-2 • TYPE 1B (316,000 W/O FRONTAGE INCREASE) • ACTUAL: 29,041SF
9508.3 NONSEPARATED OCCUPANCIES:N/Ahttps://up.codes/viewer/texas/ibc-2015/chapter/5/general-building-heights-and-areas#508.3https://up.codes/viewer/texas/ibc-2015/chapter/5/general-building-heights-and-areas#508.3
10508.4 SEPARATED OCCUPANCIESN/Ahttps://up.codes/viewer/texas/ibc-2015/chapter/5/general-building-heights-and-areas#508.4https://up.codes/viewer/texas/ibc-2015/chapter/5/general-building-heights-and-areas#508.4
11TABLE 601 FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS (HOURS)FOR TYPE VB STRUCTURAL FRAME: 0 HR BEARING WALLS- EXTERIOR: 0 HR BEARING WALLS-INTERIOR: 0 HR NON-BEARING WALLS-EXTERIOR (SEE TABLE 602) NON-BEARING WALLS-INTERIOR: 0 HR FLOOR CONSTRUCTION: 0 HR ROOF CONSTRUCTION: 0 HR https://up.codes/viewer/texas/ibc-2015/chapter/6/types-of-construction#601https://up.codes/viewer/texas/ibc-2015/chapter/6/types-of-construction#601
12TABLE 602 FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE SEPARATION DISTANCETYPE-VB FIRE SEPARATION DISTANCE • X < 5C = 1 HR • 5 ≤ X ≤ 10 = 1 HR • 10 ≤ X ≤ 30 = 0 HR • X ≥ 30 = 0 HR
13708.3 FIRE-RESISTANCE RATINGCORRIDORS: 1/2HR RATED DWELLING UNIT AND SLEEPING UNIT SEPARATIONS: 1/2HR RATEDhttps://up.codes/viewer/texas/ibc-2015/chapter/7/fire-and-smoke-protection-features#708.3https://up.codes/viewer/texas/ibc-2015/chapter/7/fire-and-smoke-protection-features#708.3EXCEPTIONS: 1. CORRIDOR WALLS PERMITTED TO HAVE A 1/2-HOUR FIRE-RESISTANCE RATING BY TABLE 1020.1. 2. DWELLING UNIT AND SLEEPING UNIT SEPARATIONS IN BUILDINGS OF TYPE IIB, IIIB AND VB CONSTRUCTION SHALL HAVE FIRE-RESISTANCE RATINGS OF NOT LESS THAN 1/2 HOUR IN BUILDINGS EQUIPPED THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.3.1.1.
14711.2.4.3 DWELLING UNITS AND SLEEPING UNITSBETWEEN DWELLING UNITS: 1/2HR RATEDhttps://up.codes/viewer/texas/ibc-2015/chapter/7/fire-and-smoke-protection-features#711.2.4.3https://up.codes/viewer/texas/ibc-2015/chapter/7/fire-and-smoke-protection-features#711.2.4.3EXCEPTION: HORIZONTAL ASSEMBLIES SEPARATING DWELLING UNITS AND SLEEPING UNITS SHALL BE NOT LESS THAN 1/2-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION IN A BUILDING OF TYPE IIB, IIIB AND VB CONSTRUCTION, WHERE THE BUILDING IS EQUIPPED THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.3.1.1.
15803.11 INTERIOR FINISH REQUIREMENTS BASED ON GROUPFOR SPRINKLERED R-2: INTERIOR EXIT STAIRWAYS AND RAMPS AND EXIT PASSAGEWAYS: CLASS C CORRIDORS AND ENCLOSURE FOR EXIT ACCESS STAIRWAYS AND RAMPS: CLASS C ROOMS AND ENCLOSED: CLASS Chttps://up.codes/viewer/texas/ibc-2015/chapter/8/interior-finishes#803.11https://up.codes/viewer/texas/ibc-2015/chapter/8/interior-finishes#803.11
16SPRINKLERS (SECTION 903 AUTOMATIC SPRINKLER SYSTEMS):NFPA13 SPRINKLER THROUGHOUT PROJECT (R-2)https://up.codes/viewer/texas/ibc-2015/chapter/9/fire-protection-systems#903.2.8https://up.codes/viewer/texas/ibc-2015/chapter/9/fire-protection-systems#903.2.8
17SECTION 1020 CORRIDORSCORRIDORS: 1/2HR RATED SEE SECTION 1021 EGRESS BALCONIES FOR CORRIDOR RATING AT EXTERIOR WALLhttps://up.codes/viewer/texas/ibc-2015/chapter/10/means-of-egress#1020https://up.codes/viewer/texas/ibc-2015/chapter/10/means-of-egress#1020
18SECTION 1004 OCCUPANT LOADTABLE 1004.1.2 MAXIMUM FLOOR AREA ALLOWANCES PER OCCUPANT RESIDENTIAL: 200 GROSShttps://up.codes/viewer/texas/ibc-2015/chapter/10/means-of-egress#1004.1.2https://up.codes/viewer/texas/ibc-2015/chapter/10/means-of-egress#1004.1.2
191006.2.1 EGRESS BASED ON OCCUPANT LOAD AND COMMON PATH OF EGRESS TRAVEL DISTANCE:FOR R-2 MAXIMUM COMMON PATH WITH SPRINKLER SYSTEM: 125FT MAXIMUM OCCUPANT LOAD OF SPACE WITH ONE EXIT: 49 https://up.codes/viewer/texas/ibc-2015/chapter/10/means-of-egress#1006.2.1https://up.codes/viewer/texas/ibc-2015/chapter/10/means-of-egress#1006.2.1
20SECTION 1017 EXIT ACCESS TRAVEL DISTANCE:FOR R-2: 250 (W/SPRINKLER) https://up.codes/viewer/texas/ibc-2015/chapter/10/means-of-egress#1017https://up.codes/viewer/texas/ibc-2015/chapter/10/means-of-egress#1017
211020.4 DEAD ENDS:50FT (WITH NFPA13 SPRINKLERS)https://up.codes/viewer/texas/iebc-2015/chapter/8/alterations-level-2#805.6HTTPS://UP.CODES/VIEWER/TEXAS/IBC-2015/CHAPTER/10/MEANS-OF-EGRESS#1020.4https://up.codes/viewer/texas/iebc-2015/chapter/8/alterations-level-2#805.6
22SECTION 1021 EGRESS BALCONIESEXTERIOR EGRESS BALCONIES SHALL BE SEPARATED FROM THE INTERIOR OF THE BUILDING BY WALLS AND OPENING PROTECTIVES AS REQUIRED FOR CORRIDORS. SECTION 1020 CORRIDORS 1020.1 CONSTRUCTION CORRIDORS SHALL BE FIRE-RESISTANCE-RATED IN ACCORDANCE WITH TABLE 1020.1. THE CORRIDOR WALLS REQUIRED TO BE FIRE-RESISTANCE-RATED SHALL COMPLY WITH SECTION 708 FOR FIRE PARTITIONS. EXCEPTIONS: CORRIDORS ADJACENT TO THE EXTERIOR WALLS OF BUILDINGS SHALL BE PERMITTED TO HAVE UNPROTECTED OPENINGS ON UNRATED EXTERIOR WALLS WHERE UNRATED WALLS ARE PERMITTED BY TABLE 602 AND UNPROTECTED OPENINGS ARE PERMITTED BY TABLE 705.8.https://up.codes/viewer/texas/ibc-2015/chapter/10/means-of-egress#1021.2https://up.codes/viewer/texas/ibc-2015/chapter/10/means-of-egress#1021.2
232902.1 MINIMUM NUMBER OF FIXTURESCLASSIFICATION & OCCUPANCY: --- R-2 • WATER CLOSETS: 1 PER DWELLING • LAVATORIES: 1 PER DWELLING • BATHTUBS/ SHOWERS: 1 PER DWELLINGhttps://up.codes/viewer/texas/ibc-2015/chapter/29/plumbing-systems#2902.1https://up.codes/viewer/texas/ibc-2015/chapter/29/plumbing-systems#2902.1CLASSIFICATION & OCCUPANCY: --- R-2 • WATER CLOSETS: 1 PER DWELLING • (REQUIRED/PROVIDED) 71/88 • LAVATORIES: 1 PER DWELLING • (REQUIRED/PROVIDED) 71/88 --- A-2 (44 OCCUPANTS) • WATER CLOSETS: 1 PER 75 • WOMEN: .29 • MEN: .29 • LAVATORIES: 1 PER 75 • WOMEN: .29 • MEN: .29